Design of Prestressed Concrete Structures
This section covers the following topics
- Calculation of Demand
- Design of Sections for Axial Tension
Introduction
The design of prestressed
concrete members can be done by the limit states method as given in Section 4
of IS: 1343 - 1980. First, the force demand in a member under the design loads
is determined from a structural analysis. A preliminary size of the member is
assumed for analysis. Next, the member is designed to meet the demand. If necessary,
another cycle of analysis and design is performed. The following material
explains the calculation of the demand in a member under the design loads.
1.1 Calculation of Demand
In the limit states method, the
design loads are calculated from the characteristics loads by multiplying them
with load factors (f). Several types of loads are considered to act together
under the selected load combinations.
The load factors are included in the load combinations as weightage
factors. The demand in a member for a particular type of load is obtained from
the analysis of the structure subjected to the characteristic value of
the load. The demands for the several load types are then combined under the
load combinations, based on the principle of superposition.
Characteristics Loads
For dead loads, a characteristic load is defined as the value which has a 95% probability of not being exceeded during the life of the structure. This concept assumes a normal distribution of the values of a particular dead load. In the following figure, the shaded area above the characteristic value represents 5% probability of exceedance of the load in the design life of the structure.
For dead loads, a characteristic load is defined as the value which has a 95% probability of not being exceeded during the life of the structure. This concept assumes a normal distribution of the values of a particular dead load. In the following figure, the shaded area above the characteristic value represents 5% probability of exceedance of the load in the design life of the structure.
For live load, wind load and
earthquake load, a characteristic load is defined based on an extreme value distribution. For example, the characteristic wind load is
defined as the value which has a 98% probability of not being exceeded during a
year.
The characteristics loads can be
obtained from IS:875 - 1987 (Code of Practice for Design Loads for Buildings
and Structures) and IS:1893 - 2002 (Criteria for Earthquake Resistant Design of
Structures) as follows.
For special loads, there are some
guidelines in IS: 875 - 1987, Part 5. In addition, specialised literature may
be referred to for these loads. The special loads are listed below.
§ Hydrostatic
§ Soil pressure
§ Fatigue
§ Accidental load
§ Impact and collision
§ Explosions
For special situations, the loads
are determined from testing of prototype
specimens. Dynamic load tests, wind tunnel tests, shake table tests are some
types of tests to determine the loads on a structure. Finite element analysis is used to determine
the stresses due to concentrated forces and dynamic loads.
Load Factors and Load
Combinations
The load factors and the
combinations of the various types of loads are given in Table 5 of IS:1343 -
1980. The following are the combinations for the ultimate condition.
a) 1.5
(DL + LL) b) 1.2 (DL + LL + WL)
c) 1.2 (DL + LL + EL)
d) 1.5 (DL + EL)
e) 1.5 (DL + WL)
f) 0.9 DL + 1.5 EL
The load combinations for service conditions are as follows.
a) DL + LL
b) DL + 0.8 (LL EL)
c) DL + EL
d) DL + WL
Analysis of Structures
Regarding analysis of structures,
IS:1343 - 1980 recommends the same
procedure as stated in IS:456 - 2000. A
structure can be analysed by the linear elastic theory to calculate the
internal forces in a member subjected to a particular type of load.
Design of Members
There can be more than one way to
design a member. In design, the number of unknown quantities is larger than the
number of available equations. Hence, some quantities need to be assumed at the
beginning. These quantities are subsequently checked.
The member can be designed either
for the service loads or, for the ultimate loads. The procedure given here is
one of the possible procedures. The design is based on satisfying the allowable
stresses under service loads and at transfer.
Initially, a lumpsum estimate of the losses is considered under service
loads. After the first round of design,
detailed computations are done to check the conditions of allowable
stresses. Precise values of the losses
are computed at this stage. The section
is then analysed for the ultimate capacity. The capacity should be greater than the demand under ultimate loads to
satisfy the limit state of collapse.
1.2 Design of Sections for Axial Tension
Introduction
Prestressed members under axial
loads only, are uncommon. Members such as hangers and ties are subjected to
axial tension. Members such as piles may
have bending moment along with axial compression or tension.
Design of Prestressing Force
First, a preliminary
dimension of the member is selected based on the architectural requirement. The
prestressing force at transfer (P0) should be such that the compressive
stress in concrete is limited to the allowable value. At service, the designed prestressing force
(Pe) should be such that the tensile stress in concrete should
be within the allowable value. The
amount of prestressing steel (Ap)
is determined from the designed prestressing force based on the allowable
stress in steel.
At transfer, in absence of
non-prestressed reinforcement, the stress in concrete (fc) is given as
follows.
Here,
Ac = net area of concrete
P0 = prestress at transfer after short-term
losses.
In presence of non-prestressed
reinforcement, the stress in the concrete (fc) can be calculated
as follows.
Here,
As = area of
non-prestressed reinforcement
Es = modulus of
elasticity of steel
Ec = modulus of
elasticity of concrete.
Here,
At = transformed
area of section
P = external axial force
Pe = effective
prestress.
The external axial force is
considered positive if it is tension and negative if it is compression. In the above expression, non-prestressed
reinforcement is not considered. If
there is non-prestressed reinforcement, Ac is to be substituted
by (Ac + (Es/Ec) As)
and At is to be calculated including As.
Analysis of Ultimate Strength
The ultimate tensile strength of
a section (PuR) is calculated as per Clause 22.3, IS: 1343 -
1980. The ultimate strength should be greater than the demand due to factored
loads.
In absence of non-prestressed
reinforcement, the ultimate tensile strength of a section (PuR)
is given as follows.
In the previous equations,
fy = characteristic yield stress for
non-prestressed reinforcement with mild steel bars
fy = characteristic
0.2% proof stress for non-prestressed reinforcement with high yield
strength deformed bars.
fpk =
characteristic tensile strength of prestressing tendons.